Frameless plaster-in ceiling air valve for 100mm ductwork. Only a thin ring-shaped air slot shows after painting.
- Ceiling cut-out: 242mm
- Plasterboard: 13mm to 26mm, one or two layers
- Supply or extract air, balancing valve included
- Fits metal, flexible or 75/90mm plastic duct systems
Ergovent Rondo 100mm plaster-in ceiling diffuser (frameless, 242mm cut-out)
The Ergovent Rondo 100mm is a plaster-in air valve for 100mm ducts. It is an invisible ceiling diffuser made of gypsum and plastered into a plasterboard ceiling. Only a thin ring-shaped air slot shows after the ceiling is skimmed and painted. It works for supply and extract air.
The Rondo 100mm and 125mm share the same 242mm ceiling cut-out and body. Only the duct connection differs. Ergovent calls the Rondo a frameless ventilation diffuser: there is no grille, frame or visible edge once the ceiling is finished.
Rondo 100mm specification
| Specification | Rondo 100mm |
|---|---|
| Duct connection | 100mm |
| Ceiling cut-out | 242mm diameter |
| Face diameter | 238mm |
| Body width | 234mm, plus two plaster mesh fixing tabs of 38mm x 120mm |
| Overall height | 89mm: 48mm body and a 41mm duct spigot |
| Plasterboard thickness | 13mm to 26mm, one or two layers |
| Air direction | Supply and extract |
| Balancing valve | Included: polyurethane damper with settings D0 to D7 |
| Material | Gypsum (plaster), paintable |
| Manufacturer | Ergovent |
| Recognition | Design Plus 2023 winner |
Supply and extract charts for the Rondo 100mm, and an air velocity chart, are in the Rondo 100/125 data sheet.
Where the Rondo 100mm is used
The Rondo is specified where a visible grille would spoil the ceiling. Typical projects include:
- Luxury homes and new builds
- Architect-designed houses and high-end apartments
- Boutique hotels
- Contemporary offices
- Interior-led commercial spaces
Inside those projects it suits bedrooms, living spaces, offices and hotel rooms. In bathrooms and other humid rooms, finish it with a moisture-resistant primer and ceiling paint, as the finishing section below explains.
What you need to install the Rondo 100mm
You need the Rondo, a duct to connect it to, and the materials to finish the ceiling around it. Ergovent's Rondo installation manual shows the steps for every size.
- The Rondo 100mm, supplied with its balancing valve
- A 100mm duct, or 75mm or 90mm flexible plastic ducts with a connection box
- A plasterboard saw or cutter for the 242mm hole
- A spirit level, and a drill with screws for the mesh fixing tabs
- Mounting tape, if the Rondo needs holding in place before the boards go up
- Primer, joint filler, thin glass fabric and ceiling paint for the finish
Which installation method suits your duct?
The installation method depends on the duct system and on whether the plasterboard is already up. Ergovent gives four methods.
| Method and duct | How it connects | Ceiling stage |
|---|---|---|
| 1. Metal ducts | Through a soft flexible duct | Boards already up; hole cut in them |
| 2. Metal ducts | Directly into the metal duct | Duct set to height, then the boards go up |
| 3. Flexible plastic ducts, 75mm or 90mm | Into the connection box tube | Before the boards go up |
| 4. Any duct system | Onto a solid duct | After the boards are up |
Frameless diffusers need slightly more space above the ceiling than framed ones. For methods 2 and 3 the manual sets the duct end 4.5cm above the ceiling line for one layer of plasterboard and 3.5cm for two layers. As drawn in the manual, keep the vertical duct at least 8cm from the ceiling framing, and keep the horizontal duct run at least 7cm above the ceiling with one layer of plasterboard or 6cm with two. For method 4, leave at least 8.5cm of straight duct between the ceiling and any bend, then trim the duct to 5.5cm as the manual shows.
Fitting the Rondo 100mm, step by step
These steps follow installation method 1, for metal ducts with a flexible connection.
- Cut a 242mm hole in the plasterboard.
- Cut a small notch at the edge of the hole, as shown in the manual.
- Pull the flexible duct through the hole.
- Fit the duct over the Rondo's 100mm spigot and secure it with a duct clip.
- Tilt the Rondo up through the hole so the mesh tabs rest on top of the board.
- Level it so its face sits about 1mm below the plasterboard.
- Screw up through the plasterboard into the mesh tabs.
The manual shows one-layer and two-layer fitting for each method.
How to finish the ceiling around the Rondo 100mm
The finish decides whether the Rondo stays invisible. Ergovent recommends the Knauf finishing system:
- Remove dust from the surfaces and gaps you will fill.
- Prime with Ceresit CT-17 or Knauf Tiefgrund.
- Fill the gaps with Knauf Fugenfuller or Uniflott filler.
- Cover the whole diffuser surface with thin glass fabric so the joint does not crack.
- Apply a deep primer over the filled areas before painting.
- Paint the ceiling and the Rondo's outer ring together.
- Paint the removable centre plate separately, then refit it.
In humid rooms use a moisture-resistant primer and a ceiling paint made for humid rooms.
Which Rondo size do you need?
Choose the Rondo that matches your duct diameter. The Rondo 100mm uses the same 242mm ceiling cut-out as the Rondo 125mm.
| Model | Duct | Ceiling cut-out |
|---|---|---|
| Rondo 100mm (this page) | 100mm | 242mm |
| Rondo 125mm | 125mm | 242mm |
| Rondo 150mm | 150mm | 300mm |
| Rondo 160mm | 160mm | 300mm |
The Rondo 100mm and 125mm have a 238mm face, stand 89mm high and won the Design Plus award in 2023. The Rondo 150mm and 160mm have a 296mm face, stand 91mm high and won a Red Dot award in 2023.
How to balance airflow on the Rondo 100mm
Each Rondo comes with an Ergovent balancing valve: a polyurethane damper inserted in the diffuser's connection sleeve. You balance the system by changing the number of removable segments. On the Rondo 100mm and 125mm, each setting adds one more segment, from D0 with no damper to D7 with seven.
| Setting | Damper (Rondo 100 and 125) | Airflow |
|---|---|---|
| D0 | No damper | Fully open |
| D1 | 1 segment inserted | Reduced |
| D2 | 2 segments inserted | Reduced further |
| D3 | 3 segments inserted | Reduced further |
| D4 | 4 segments inserted | Reduced further |
| D5 | 5 segments inserted | Reduced further |
| D6 | 6 segments inserted | Reduced further |
| D7 | 7 segments inserted | Lowest |
The Rondo 100/125 data sheet charts pressure drop against airflow for settings D0 to D4 on the Rondo 100mm, for supply and for extract. Ask us for D5 to D7 figures before you balance a system.
Rondo or Kvadro?
Choose the Rondo for a round ring in the ceiling and the Ergovent Kvadro for a square outline. Both give the same flush plaster-in finish.
See the Ergovent Kvadro range.
Rondo 100mm questions
Can the Rondo 100mm be fitted to an existing ceiling?
Yes, if the ceiling is plasterboard and a duct already reaches the spot. Method 1 suits a flexible duct you can pull through the 242mm hole. Method 4 suits a solid duct that already passes through the board: you trim it, fit the Rondo, turn it 90 degrees and glue the cut-out board pieces back over the fixing tabs. Then fill, prime and repaint the area. It is easiest to plan in at the ceiling stage.
Does the Rondo work for extract as well as supply?
Yes. Ergovent publishes separate supply and extract charts for the Rondo 100mm.
Can I paint the Rondo?
Yes. The gypsum body takes the same primer and paint as the ceiling.
Will it fit a double-layer ceiling?
Yes. The Rondo suits plasterboard from 13mm to 26mm thick, in one or two layers.
Can I use it with a 75mm or 90mm plastic duct system?
Yes. Installation method 3 connects the Rondo to 75mm or 90mm flexible plastic ducts through a connection box.
How do I adjust the airflow after fitting?
Take off the removable centre plate, change the damper segments in the connection sleeve, then refit the plate. Settings run from D0 with no damper to D7 with seven segments.